πŸ”—Breaker and wire size chart

βœ“ Tested & verified Updated: How we calculate this

At a 75 Β°C terminal on a short run: 15 A takes 14 AWG copper, 20 A takes 12, 30 A takes 10, 40 A takes 8, 50 A takes 8, 60 A takes 6, 100 A takes 3, and 200 A takes 3/0. Aluminium is two sizes larger.

Notice that 40 A and 50 A share a conductor. 8 AWG copper carries 50 A, so it covers both β€” the pairing is a floor, not a one-to-one mapping.

Three things move any row of this chart: 240.4(D) caps 14, 12 and 10 AWG regardless of the table, a continuous load raises the current by 25% before you start, and distance can push the conductor up without changing the breaker at all.

The chart

Breaker rating against the smallest conductor that carries it at 75 °C, with no derating and a short run. Computed from NEC Table 310.16, 240.4(D) and Table 250.122.
BreakerCopperAluminiumCopper groundWhat it usually feeds
15 A14 AWG12 AWG14 AWGLighting and general receptacles
20 A12 AWG12 AWG12 AWGKitchen, bathroom and garage receptacles
30 A10 AWG10 AWG10 AWGDryer, small water heater, RV outlet
40 A8 AWG8 AWG10 AWGRange, 40 A EV charger
50 A8 AWG6 AWG10 AWGRange, welder, 50 A EV charger, hot tub
60 A6 AWG4 AWG10 AWGSub panel, large hot tub, tankless heater
70 A4 AWG3 AWG8 AWGSub panel, larger tankless heater
100 A3 AWG1 AWG8 AWGSub panel, or a small service
125 A1 AWG2/0 AWG6 AWGSub panel
150 A1/0 AWG3/0 AWG6 AWGService, or a large sub panel
200 A3/0 AWG250 kcmil6 AWGTypical whole-house service

The three rules that move a row

240.4(D), the small-conductor rule. 14 AWG copper is held to 15 A, 12 AWG to 20 A and 10 AWG to 30 A β€” whatever Table 310.16 says they can carry. It is why 12 AWG reads 25 A in the table and is still a 20 amp circuit, and it is the difference between the ampacity chart and this one.

Continuous loads. Anything on for three hours or more is taken at 125%. A 40 A EV charger is a 50 A circuit; a 48 A charger is a 60 A circuit. The device moves and the conductor moves with it.

Distance. Voltage drop can force the conductor up two sizes on a long run while the breaker stays exactly where it was. When that happens, 250.122(B) pulls the ground up in the same proportion, and that is the step most people miss.

In cable rather than conduit

Non-metallic sheathed cable is used at the 60 Β°C ampacity under 334.80, so the pairing changes:

CircuitIn conduit (THHN)In NM cable
15 A14 AWG14/2
20 A12 AWG12/2
30 A10 AWG10/3
40 A8 AWG8/3
50 A8 AWG6/3
60 A6 AWG4/3

The 50 and 60 A rows are where the two columns part company, and it is exactly the range where hot tubs, tankless heaters and sub panels live.

What each circuit usually feeds

The right-hand column of the main chart is the practical version of this whole page. Two rows are worth calling out because they are the ones people get wrong:

30 A at 240 V is a dryer or a small water heater β€” and it is also the largest circuit that 10 AWG can serve, so it is the natural ceiling of a Romex-only installation.

60 A at 240 V is where sub panels start, and where the cable-versus-conduit distinction stops being academic. A 60 A feeder in NM cable is 4/3, which is expensive and stiff; the same feeder in conduit is 6 AWG. That difference decides the wiring method on a lot of garage projects.

Work out your own pairing, including distance and derating, on the breaker size calculator or the wire size calculator.

Frequently asked questions

What size wire for a 60 amp breaker?

6 AWG copper or 4 AWG aluminium at 75 Β°C, with a 10 AWG copper ground. In NM cable it is 6/3, which is rated 55 A on the 60 Β°C column β€” so a full 60 A load in Romex needs 4/3. That gap between cable and conduit conductors catches people on sub panel feeds and tankless heaters.

Can I use a 30 amp breaker on 12 gauge wire?

No. 240.4(D) holds 12 AWG copper to a 20 amp device whatever the ampacity table says, so a 30 A breaker on 12 AWG leaves the conductor unprotected. This is the most common unsafe modification in domestic wiring, and it usually starts with a breaker that kept tripping.

Why do 40 and 50 amp circuits use the same wire?

Because 8 AWG copper carries 50 A at 75 Β°C, which covers a 40 A circuit with room to spare. The chart gives the smallest conductor each device may protect; using the same size for both is normal and means an existing 40 A circuit can often be uprated to 50 by changing the breaker β€” after checking the terminals and the load.

Does the ground wire scale with the breaker?

It scales in steps rather than continuously: everything from 25 to 60 A uses a 10 AWG copper ground, 70 to 100 A uses 8 AWG, and 110 to 200 A uses 6 AWG. Table 250.122 is indexed on the device rating, not on the conductor size, so upsizing the hots does not by itself change the ground β€” unless you upsized them for voltage drop, and then 250.122(B) does.

Is this chart the same for a feeder as for a branch circuit?

The conductor arithmetic is the same, but two things differ. A feeder normally carries a neutral, which changes the conduit and can change the derating count. And a dwelling service or main feeder may use the 83% allowance of 310.12, which lets a 100 A feeder be 4 AWG copper instead of 3.

How we calculate this

The chart is computed at build time from the same data the calculators read: allowable ampacity from NEC Table 310.16 at 75 Β°C, the standard device ratings of 240.6(A), the small-conductor ceiling of 240.4(D), and the equipment grounding conductor from Table 250.122. It assumes a non-continuous load, an ambient of 86 Β°F (30 Β°C), no more than three current-carrying conductors in the raceway, and a run short enough that voltage drop does not govern. Each of those four assumptions can move a row, which is what the calculators are for.

Sources:

One circuit check a month

Monthly

One thing a month worth measuring, testing or recalculating on a home electrical system β€” the part of sizing that happens after the install. No product pitches, and nothing that needs a live panel.

Free, no account. One click unsubscribes and deletes your address.