πŸ“‹NEC conduit fill chart

βœ“ Tested & verified Updated: How we calculate this

The limit is 53% of the raceway’s internal area for one conductor, 31% for exactly two, and 40% for three or more β€” NEC Chapter 9, Table 1. A nipple no longer than 24 inches gets 60%.

Two conductors getting the tightest allowance looks like a misprint and is not: two round conductors of similar diameter can wedge against each other going round a bend in a way three cannot.

In practice the numbers are generous. Half-inch EMT takes nine 12 AWG THHN conductors at 40%, which is more than anybody pulls β€” the friction of four bends and the derating for more than three current-carrying conductors both bite long before the area does.

EMT β€” thin-wall steel

The most common raceway in commercial interiors, and the reference everyone quotes.

EMT (thin-wall steel) β€” how many THHN or THWN-2 conductors of one size fit at the 40 % fill limit. Computed from NEC Chapter 9, Table 4 and Table 5.
Conductor1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1221356183138241364476608
12 AWG916254461100176266347443
10 AWG51016283863111167218279
8 AWG3591622366496126161
6 AWG246111626466991116
4 AWG124791628425671
3 AWG123681324364760
2 AWG112571120303950
1 AWG1235815222937
1/0 AWG1134712192431
2/0 AWG123610152026
3/0 AWG12358131722
4/0 AWG11247101418
250 kcmil123581114
300 kcmil112571012
350 kcmil11246811
400 kcmil11236710
500 kcmil113568
600 kcmil12456
700 kcmil12345
750 kcmil12345

PVC Schedule 40

Underground, outdoors, and in slabs. Slightly less room than EMT of the same trade size.

PVC Schedule 40 β€” how many THHN or THWN-2 conductors of one size fit at the 40 % fill limit. Computed from NEC Chapter 9, Table 4 and Table 5.
Conductor1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1120345981135193299401517
12 AWG81525435998141218292377
10 AWG591527376289137184237
8 AWG3591521355179106137
6 AWG24611152537577699
4 AWG124791522354760
3 AWG123581319294051
2 AWG12561116253343
1 AWG1235812182432
1/0 AWG1134710152027
2/0 AWG12358131722
3/0 AWG12247101418
4/0 AWG1124581215
250 kcmil12347912
300 kcmil11246810
350 kcmil1123579
400 kcmil123468
500 kcmil112457
600 kcmil12345
700 kcmil11235
750 kcmil11234

PVC Schedule 80

Where physical protection is needed β€” exposed risers, bollards. The thicker wall costs real capacity.

PVC Schedule 80 β€” how many THHN or THWN-2 conductors of one size fit at the 40 % fill limit. Computed from NEC Chapter 9, Table 4 and Table 5.
Conductor1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG816285170118169265358464
12 AWG61220375186123193261338
10 AWG471323325478122164213
8 AWG247131831457094123
6 AWG1359132232506888
4 AWG113681319314254
3 AWG12571116263546
2 AWG1245914223038
1 AWG1134710162228
1/0 AWG12368131824
2/0 AWG12357111520
3/0 AWG1124691216
4/0 AWG123571013
250 kcmil11246811
300 kcmil1123579
350 kcmil123468
400 kcmil112457
500 kcmil12346
600 kcmil11245
700 kcmil11234
750 kcmil11234

Rigid metal conduit

RMC (rigid metal) β€” how many THHN or THWN-2 conductors of one size fit at the 40 % fill limit. Computed from NEC Chapter 9, Table 4 and Table 5.
Conductor1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1222366285140200309412531
12 AWG916264562102146225301387
10 AWG5101628396492142189244
8 AWG3691622375381109140
6 AWG246121626385978101
4 AWG1247101623364862
3 AWG123681420304152
2 AWG113571116253444
1 AWG1235812192532
1/0 AWG1134710162127
2/0 AWG12368131823
3/0 AWG12357111419
4/0 AWG1124691215
250 kcmil123471012
300 kcmil11246811
350 kcmil1123579
400 kcmil1123568
500 kcmil112457
600 kcmil12345
700 kcmil11345
750 kcmil11234

Flexible metal conduit

Short connections to motors and fixtures, where movement or vibration rules out solid pipe.

FMC (flexible metal, greenfield) β€” how many THHN or THWN-2 conductors of one size fit at the 40 % fill limit. Computed from NEC Chapter 9, Table 4 and Table 5.
Conductor1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1321335276134202291396518
12 AWG91624385598147212289377
10 AWG6101524356193134182238
8 AWG3581320355377105137
6 AWG24610142538557599
4 AWG123691523344661
3 AWG123571320293951
2 AWG112461116243343
1 AWG1234812182432
1/0 AWG1124710152027
2/0 AWG12358121722
3/0 AWG11247101418
4/0 AWG1124681115
250 kcmil11347912
300 kcmil11246810
350 kcmil123579
400 kcmil123468
500 kcmil112357
600 kcmil12345
700 kcmil11235
750 kcmil11234

Reading these charts properly

They assume one conductor size throughout. A mixed pull needs the area arithmetic, which the conduit fill calculator does with two sizes at once.

They are area limits, not pulling limits. Total bends between pull points are capped at 360 degrees, and friction climbs much faster than fill percentage. A 38% pull through four bends is harder work than 40% through one.

They say nothing about ampacity. Once more than three current-carrying conductors share the raceway, Table 310.15(C)(1) reduces what every one of them can carry: 80% at four to six, 70% at seven to nine, 50% at ten to twenty. Filling a pipe to 40% with current-carrying conductors usually removes the reason you wanted to.

XHHW-2 is not THHN. In small sizes XHHW-2 is slightly fatter and in large sizes slightly slimmer, so it can change a borderline answer in either direction. Switch the insulation in the calculator rather than assuming.

Frequently asked questions

How many wires can I put in 3/4 inch conduit?

Sixteen 12 AWG THHN or ten 10 AWG at the 40% limit in three-quarter inch EMT. For 8 AWG it is five, for 6 AWG four, and for 4 AWG two. Those are area limits and not practical ones: pulling sixteen conductors through a run with two bends is unpleasant, and all sixteen would be derated to 50% of their ampacity.

Does the ground count in conduit fill?

Yes. Fill is about physical space, so every conductor in the raceway counts β€” grounds, neutrals, travellers, spare pull strings if they were conductors. Derating is the opposite: the equipment grounding conductor never counts there, and the neutral of a balanced multiwire circuit does not either. The two rules count different things because they are measuring different problems.

Is PVC the same as EMT for fill?

Close but not identical. PVC Schedule 40 has a slightly smaller internal area than EMT of the same trade size, and Schedule 80 is noticeably smaller because the wall is thicker. A pull that just fits half-inch EMT can be over the line in half-inch Schedule 80, which is the trap when a plan changes from indoor to underground.

What is the 60 percent nipple rule?

A raceway not exceeding 24 inches in length between two enclosures may be filled to 60%, per Chapter 9, Note 4. The reasoning is that nothing is really being pulled any distance and heat escapes at both ends. It is genuinely useful between a meter and a panel, and it does not extend to a short piece of a long run.

Can I mix conductor sizes in one conduit?

Yes, and it is normal β€” a feeder with a smaller neutral or ground. The arithmetic is the sum of each conductor’s own area from Chapter 9, Table 5 against the raceway’s area from Table 4. The published charts assume one size throughout, which is why a mixed pull needs a calculation rather than a lookup.

How we calculate this

Every chart on this page is computed at build time from NEC Chapter 9: internal raceway areas from Table 4, insulated conductor cross-sections from Table 5, and permitted fill percentages from Table 1 β€” 53% for one conductor, 31% for two, 40% for more than two, and 60% for a nipple not over 24 in under Note 4. The count shown is the largest whole number of conductors of that size whose combined area does not exceed 40% of the raceway’s internal area. Where conductor sizes are mixed, the same area arithmetic applies per Note 6 and a published chart cannot be used directly.

Sources:

One circuit check a month

Monthly

One thing a month worth measuring, testing or recalculating on a home electrical system β€” the part of sizing that happens after the install. No product pitches, and nothing that needs a live panel.

Free, no account. One click unsubscribes and deletes your address.