πŸ“How We Calculate

βœ“ Tested & verified Updated:

Every calculator on this site runs the same three steps in the same order an electrician does them: work out the current, look up what the conductor can carry, then check whether the run is too long for it. Whichever of the last two asks for more copper is the answer.

The formulas

  • Voltage drop: k Γ— amps Γ— R Γ— one-way feet Γ· 1,000, where k is 2 for single-phase and DC and 1.732 for balanced three-phase, and R is ohms per 1,000 ft.
  • Percent drop: volts lost Γ· nominal system voltage Γ— 100.
  • Longest run at a target: target% Γ· 100 Γ— volts Γ— 1,000 Γ· (k Γ— amps Γ— R).
  • Continuous load: amps Γ— 1.25, per 210.19(A)(1) and 215.2(A)(1). Lighting, EV charging and process heat are continuous; a general receptacle circuit is not.
  • Usable ampacity: table ampacity Γ— ambient factor Γ— bundling factor.
  • Conduit fill: total conductor area Γ· internal raceway area. The ceiling is 53% for one conductor, 31% for two, 40% for more than two, and 60% in a nipple no longer than 24 in.
  • Box fill: a volume allowance for every conductor, twice the largest conductor for each device yoke, one allowance for all internal clamps together, one for all grounding conductors together.
  • Motors: conductors at 125% of the table full-load current (430.22), inverse-time breaker up to 250% (430.52), overload relay at 115–125% of the nameplate current (430.32).
  • Transformers: kVA Γ— 1,000 Γ· (k Γ— volts) on each side, then 125% of that current for the protective device.

The tables we read, and where they are

WhatNEC tableWhat we use it for
Allowable ampacityTable 310.1660, 75 and 90 Β°C columns, copper and aluminium
Ambient correctionTable 310.15(B)(1)anything hotter or colder than 86 Β°F (30 Β°C)
Bundling adjustmentTable 310.15(C)(1)more than three current-carrying conductors together
Small-conductor ceiling240.4(D)14 AWG at 15 A, 12 at 20, 10 at 30
Standard device ratings240.6(A)rounding a load up to a breaker that exists
Equipment grounding conductorTable 250.122the ground wire, and 250.122(B) when the circuit is upsized
Conductor area and resistanceChapter 9, Table 8kcmil, mmΒ², diameter, ohms per 1,000 ft
Insulated conductor areaChapter 9, Table 5THHN/THWN-2 and XHHW-2 cross-sections
Raceway internal areaChapter 9, Table 4EMT, PVC 40 and 80, RMC, IMC, ENT, FMC
Fill percentagesChapter 9, Table 153 / 31 / 40 %, and the nipple note
Box volume allowances314.16(B) and Table 314.16(A)cubic inches needed, and the boxes that are sold
Flexible cord ampacityTable 400.5(A)(1)extension cords, which 310.16 does not cover
Motor full-load currentTables 430.248 and 430.250single-phase and three-phase motors

The full conductor table

This is the file every calculator on the site reads. The reference pages draw the same rows, so a chart here and an answer in a widget cannot disagree.

Conductor size, area, resistance and allowable ampacity. Ampacity is NEC Table 310.16 β€” not more than three current-carrying conductors in a raceway, cable or earth, at 86 °F (30 °C) ambient. Correct it for heat and for bundling before you use it.
Sizekcmilmm²Cu 60 °CCu 75 °CCu 90 °CAl 75 °CCu Ω/kftAl Ω/kft
14 AWG4.112.0815 A20 A25 A3.14
12 AWG6.533.3120 A25 A30 A20 A1.983.18
10 AWG10.385.26130 A35 A40 A30 A1.242
8 AWG16.518.36740 A50 A55 A40 A0.7781.26
6 AWG26.2413.355 A65 A75 A50 A0.4910.808
4 AWG41.7421.1570 A85 A95 A65 A0.3080.508
3 AWG52.6226.6785 A100 A115 A75 A0.2450.403
2 AWG66.3633.6295 A115 A130 A90 A0.1940.319
1 AWG83.6942.41110 A130 A145 A100 A0.1540.253
1/0 AWG105.653.49125 A150 A170 A120 A0.1220.201
2/0 AWG133.167.43145 A175 A195 A135 A0.09670.159
3/0 AWG167.885.01165 A200 A225 A155 A0.07660.126
4/0 AWG211.6107.2195 A230 A260 A180 A0.06080.1
250 kcmil250127215 A255 A290 A205 A0.05150.0847
300 kcmil300152240 A285 A320 A230 A0.04290.0707
350 kcmil350177260 A310 A350 A250 A0.03670.0605
400 kcmil400203280 A335 A380 A270 A0.03210.0529
500 kcmil500253320 A380 A430 A310 A0.02580.0424
600 kcmil600304350 A420 A475 A340 A0.02140.0353
700 kcmil700355385 A460 A520 A375 A0.01840.0303
750 kcmil750380400 A475 A535 A385 A0.01710.0282

Where the figures come from

Ampacity, resistance, conductor area, raceway area, fill percentages and motor currents are all published in NFPA 70, the National Electrical Code; NFPA provides free read-only access to the current edition, and each table is named above so you can check any number against it. Extension cord ampacity is Table 400.5(A)(1), which is a different table from 310.16 for a reason: a cord is not a raceway. Nothing on this site is an estimate, an average of several sources, or a figure remembered from a job.

Units: US first, metric one tap away

Feet, Fahrenheit, AWG and horsepower are the units the NEC tables are written in, so they are the defaults. None of them means anything to most of the world, so every physical quantity on this site has a switch beside the field, and the choice travels in the link.

QuantityDefaultAlternativeExactly
Conductor sizeAWG, kcmilmmΒ²1 kcmil = 0.50670748 mmΒ²
Run lengthfeetmetres1 ft = 0.3048 m
Ambient temperatureΒ°FΒ°CΒ°C = (Β°F βˆ’ 32) Γ— 5/9
Motor ratinghorsepowerkilowatts1 mechanical HP = 745.7 W
Box volumecubic inchescmΒ³1 cu in = 16.387064 cmΒ³
Tray width, conductor diameterinchesmillimetres1 in = 25.4 mm

Volts, amps, watts, ohms, VA and kVA get no switch, because they are SI units already.

Horsepower is two units, not one. Mechanical horsepower is 745.7 W and is what a US motor nameplate means. Metric horsepower β€” PS, CV β€” is 735.5 W. The motor calculator prints both so a nameplate can be checked against the right one.

The arithmetic never changes with the units. Inputs are converted back to the units the code tables use before they touch a table, and the results are converted on the way out. Calculations follow the US NEC; outside the US, follow your local electrical code β€” the metric columns are a conversion for reading and for buying cable, not a claim of compliance with IEC 60364 or any other national standard, whose ampacity tables are organised differently and give different figures for the same cross-section.

What this is not

It is not a design and it is not a permit. Three things routinely make the right table give the wrong answer on a real job. Your local code is not the NEC β€” states adopt different editions and add amendments, and some cities write their own. Your equipment terminals carry their own temperature rating, which is often lower than the wire’s, and the lower of the two governs. And the conditions of use β€” sun on a rooftop conduit, a bundle through insulation, a run under a slab β€” change the derating. A licensed electrician resolves all three; a calculator cannot.

Nothing you type is sent anywhere. Every calculation happens in your own browser, no account is needed for any tool, and the site keeps no record of what you worked out.

One circuit check a month

Monthly

One thing a month worth measuring, testing or recalculating on a home electrical system β€” the part of sizing that happens after the install. No product pitches, and nothing that needs a live panel.

Free, no account. One click unsubscribes and deletes your address.