What size ground wire do you need?
Ground wire size calculator
8 AWG copper ground
behind a 100 A device · that is 8.4 mm²
| Device rating | Copper ground | Aluminium ground |
|---|---|---|
| 15 A and below | 14 AWG | 12 AWG |
| 20 A and below | 12 AWG | 10 AWG |
| 60 A and below | 10 AWG | 8 AWG |
| 100 A and below | 8 AWG | 6 AWG |
| 200 A and below | 6 AWG | 4 AWG |
| 300 A and below | 4 AWG | 2 AWG |
| 400 A and below | 3 AWG | 1 AWG |
| 500 A and below | 2 AWG | 1/0 AWG |
| 600 A and below | 1 AWG | 2/0 AWG |
| 800 A and below | 1/0 AWG | 3/0 AWG |
| 1000 A and below | 2/0 AWG | 4/0 AWG |
| 1200 A and below | 3/0 AWG | 250 kcmil |
- Copper option
- 8 AWG
- Aluminium option
- 6 AWG
Upsized 1.00× for drop, so 250.122(B) makes the ground 8 AWG.
Upsized the circuit for voltage drop? Set both size boxes and the ground grows with it.
A sizing aid from the published NEC tables, not a design โ have it signed off by a licensed electrician against the code your inspector enforces. Calculations follow the US NEC; outside the US, follow your local electrical code.
One circuit check a month
MonthlyOne thing a month worth measuring, testing or recalculating on a home electrical system โ the part of sizing that happens after the install. No product pitches, and nothing that needs a live panel.
Try also
What size ground wire does a circuit need?
The AmpSizer ground wire size for a 100 amp circuit is 8 AWG copper, or 6 AWG aluminium. It comes from the rating of the device ahead of the circuit, not from the size of the conductors next to it โ Table 250.122 is indexed on amps, not on wire.
That distinction matters because the two often disagree. A 100 A feeder pulled in 1 AWG aluminium and one pulled in 3 AWG copper take the same 8 AWG copper ground.
The exception is 250.122(B). If you made the circuit conductors bigger than they needed to be โ almost always for voltage drop โ the grounding conductor increases in the same proportion by area. Going from 8 AWG to 6 AWG is 1.59 times the area, so a 10 AWG ground becomes 8 AWG.
The whole table is below. It is short, it has not changed materially in decades, and it is worth knowing by heart for the sizes you use every week: 15 A takes 14, 20 A takes 12, everything from 25 to 60 A takes 10, and 100 A takes 8.
| Device rating | Copper | Aluminium | Copper in mm² |
|---|---|---|---|
| Up to 15 A | 14 AWG | 12 AWG | 2.08 mm² |
| Up to 20 A | 12 AWG | 10 AWG | 3.31 mm² |
| Up to 60 A | 10 AWG | 8 AWG | 5.261 mm² |
| Up to 100 A | 8 AWG | 6 AWG | 8.367 mm² |
| Up to 200 A | 6 AWG | 4 AWG | 13.3 mm² |
| Up to 300 A | 4 AWG | 2 AWG | 21.15 mm² |
| Up to 400 A | 3 AWG | 1 AWG | 26.67 mm² |
| Up to 500 A | 2 AWG | 1/0 AWG | 33.62 mm² |
| Up to 600 A | 1 AWG | 2/0 AWG | 42.41 mm² |
| Up to 800 A | 1/0 AWG | 3/0 AWG | 53.49 mm² |
| Up to 1000 A | 2/0 AWG | 4/0 AWG | 67.43 mm² |
| Up to 1200 A | 3/0 AWG | 250 kcmil | 85.01 mm² |
Why it is sized on amps and not on the wire
The grounding conductor has one job: carry enough fault current, for long enough, to make the overcurrent device operate. What decides that is the device โ how much current it needs to see and for how long โ not how thick the circuit conductors happen to be.
This is why the table steps in device ratings and why the same ground serves several conductor sizes. It is also why upsizing for voltage drop is treated as an exception rather than the rule: a longer run has more impedance in the fault path too, and 250.122(B) keeps the ground in proportion so the path does not get relatively weaker as the run gets longer.
Frequently asked questions
What size ground wire for a 100 amp sub panel?
8 AWG copper or 6 AWG aluminium for the equipment grounding conductor, from Table 250.122. Note that this is the ground that runs with the feeder โ it is a different question from the grounding electrode conductor at a service, which is sized from Table 250.66 and is usually 4 AWG copper for a 100 to 200 A service.
Can the ground be smaller than the neutral?
Yes, and normally it is. The neutral is a current-carrying conductor sized like a hot; the equipment grounding conductor only has to carry fault current long enough to open the breaker. On a 100 A feeder the hots and neutral might be 3 AWG copper while the ground is 8 AWG.
Does the ground wire count toward conduit fill or derating?
Toward fill yes, toward derating no. Fill is about physical space in the pipe, so every conductor counts. Derating is about heat from current, and the grounding conductor only carries current during a fault, so 310.15(C)(1) leaves it out of the count.
Do I upsize the ground when I upsize for a long run?
Yes โ 250.122(B), and it is the step most people miss. The ratio is by circular-mil area, not by size step: 8 AWG to 6 AWG is 26,240 over 16,510, or 1.59, so a 10 AWG ground goes to 8 AWG. Going up two sizes rather than one usually pushes the ground up two as well.
Is a bare ground allowed in conduit?
In most cases yes, and in metal raceway the raceway itself can serve as the equipment grounding conductor under 250.118. Many electricians pull a separate green or bare conductor anyway, because couplings and connectors are the weakest part of that path and a wire is easier to prove than a pipe.
How we calculate this
Worked example
With Breaker or fuse ahead of the circuit 100 A, Ground wire metal Copper, Circuit conductor the table expects Not upsized, Conductor you are actually pulling Same, this page works out 8 AWG copper ground. behind a 100 A device ยท that is 8.4 mmยฒ
- Copper option8 AWG
- Aluminium option6 AWG
Sources:
The three grounds that get confused
Equipment grounding conductor. The one this page sizes. It runs with the circuit, bonds the metal parts, and exists to carry fault current back so the breaker trips. Table 250.122.
Grounded conductor. The neutral. It carries normal current and is sized like a hot conductor. The code calls it “grounded”, which is exactly one letter away from the one above and the source of half the confusion in this subject.
Grounding electrode conductor. The one going to the rod, the plate or the rebar at the service. Sized from Table 250.66 and generally 4 AWG copper for a 100 to 200 A dwelling service. It has nothing to do with branch circuits.