🏑How big does the service need to be?

βœ“ Tested & verified Updated: How we calculate this

Adding up every circuit gives a number no house ever reaches. The load worksheet is the arithmetic that turns it into a service size.

One circuit check a month

Monthly

One thing a month worth measuring, testing or recalculating on a home electrical system β€” the part of sizing that happens after the install. No product pitches, and nothing that needs a live panel.

Free, no account. One click unsubscribes and deletes your address.

Free to use β€” Pro is for keeping it

This tool, like every other one here, is free and needs no account. A free account keeps three setups and three email alerts. Pro takes the ads off every site we run and lifts that to 200 setups and 50 alerts, adds a public page for any result and lets you embed the tool without our badge.

See what Pro adds Sign in

Try also

How this works

Enter each load in volt-amps with the demand factor the code gives it, and the sheet totals the calculated load. Divide by 240 for the service current: under 100 amps a 100 amp service will do, and anything over about 160 leaves too little room for a charger or a heat pump later. The spare-capacity line is not a code requirement, it is the difference between a service that lasts and one that gets upgraded twice.

The standard method, in the order the code applies it

NEC Article 220 Part III for a one-family dwelling, which is what decides the service size.

StepWhat goes inFactor
General lighting and receptacles3 VA per square foot100% of first 10 kVA, 40% of the rest
Small appliance branch circuits1,500 VA each, minimum twoincluded in general load
Laundry branch circuit1,500 VAincluded in general load
Electric rangeNameplate, per Table 220.55demand factors apply
Electric dryer5,000 VA or nameplate, whichever is greater100%
Fixed appliances, four or moreNameplate total75%
Heating or coolingThe larger of the two100%

The first 10 kVA of general load counts at 100% and everything above it at 40%. That single step is most of the difference between connected load and demand.

Frequently asked questions

What is the difference between connected load and calculated load?

Connected load is everything added up. Calculated load applies the demand factors of Article 220, because a house never runs everything at once β€” the first 10 kVA of general load counts fully and the remainder at 40%, ranges have their own table, and only the larger of heating or cooling counts. The calculated figure is what sizes the service.

Do I have to use the standard method?

No. Article 220 Part IV gives an optional method for dwellings that is simpler and often gives a smaller answer, and either is acceptable. The standard method is the one most permit applications are laid out for, which is why this sheet follows it.

How much spare capacity should a service have?

Enough for what you will add, which today usually means a charger, a heat pump or an induction range β€” each of which is 30 to 60 amps of continuous or near-continuous load. Twenty-five percent is a reasonable planning margin. Where the answer will not fit, load management is explicitly recognised by the code and costs a fraction of a service upgrade.

How we calculate this

Each row is volt-amps multiplied by the demand factor entered for it, and rows are summed before rounding. The demand factors themselves are not applied automatically, because which one applies depends on the load type and on how many similar appliances are present β€” NEC 220.42 for general lighting, Table 220.55 for ranges, 220.53 for four or more fixed appliances, 220.60 for the larger of heating and cooling. Service current is the calculated load divided by the nominal system voltage. This is the standard method of Article 220 Part III; the optional method of Part IV is an equally valid alternative that frequently gives a smaller result.