How many amps can a wire carry?
Wire ampacity calculator
25 amps usable
12 AWG reads 25 A in the table, then × 1.00 for heat × 1.00 for bundling
No derating at these conditions
| Metal | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| Copper | 20 A | 25 A | 30 A |
| Aluminium | 15 A | 20 A | 25 A |
- Largest device this supports
- 20 A
- The same ambient in Celsius
- 30 °C
240.4(D) caps this size at 20 A whatever the table says.
Count only current-carrying conductors โ the ground never counts.
A sizing aid from the published NEC tables, not a design โ have it signed off by a licensed electrician against the code your inspector enforces. Calculations follow the US NEC; outside the US, follow your local electrical code.
One circuit check a month
MonthlyOne thing a month worth measuring, testing or recalculating on a home electrical system โ the part of sizing that happens after the install. No product pitches, and nothing that needs a live panel.
Try also
How many amps can a wire carry?
The AmpSizer ampacity result for 12 AWG copper at a 75 ยฐC terminal is 25 amps โ and the circuit is still limited to a 20 amp breaker, because 240.4(D) caps small conductors regardless of what the table allows.
Both corrections come off that 25. Put six current-carrying conductors in one raceway and it becomes 20 A. Raise the ambient to 104 ยฐF as well and it becomes 17.6 A, which is below the breaker the circuit was designed around.
This is why the 90 ยฐC column rarely helps. THHN is a 90 ยฐC conductor, but 110.14(C) makes you use the temperature rating of the terminals it lands on, and almost every breaker is listed at 75 ยฐC. The 90 ยฐC figure is the number you derate from, not the one you use.
Both correction tables are below, so you can see the shape of them rather than one factor at a time. The pattern worth remembering is that ambient corrections are gentle until about 100 ยฐF and then steep, while the bundling adjustment falls off a cliff at four conductors and again at ten.
| Ambient | 60 °C wire | 75 °C wire | 90 °C wire |
|---|---|---|---|
| 50โ77 F (10โ25 C) | × 1.08 | × 1.05 | × 1.04 |
| 78โ86 F (26โ30 C) | × 1 | × 1 | × 1 |
| 87โ95 F (31โ35 C) | × 0.91 | × 0.94 | × 0.96 |
| 96โ104 F (36โ40 C) | × 0.82 | × 0.88 | × 0.91 |
| 105โ113 F (41โ45 C) | × 0.71 | × 0.82 | × 0.87 |
| 114โ122 F (46โ50 C) | × 0.58 | × 0.75 | × 0.82 |
| 123โ131 F (51โ55 C) | × 0.41 | × 0.67 | × 0.76 |
| 132โ140 F (56โ60 C) | not permitted | × 0.58 | × 0.71 |
| Current-carrying conductors | Multiply ampacity by |
|---|---|
| 1 to 3 | × 1 |
| 4 to 6 | × 0.8 |
| 7 to 9 | × 0.7 |
| 10 to 20 | × 0.5 |
| 21 to 30 | × 0.45 |
| 31 to 40 | × 0.4 |
| 41 and more | × 0.35 |
The full ampacity table
| Size | kcmil | mm² | Cu 60 °C | Cu 75 °C | Cu 90 °C | Al 75 °C | Cu Ω/kft | Al Ω/kft |
|---|---|---|---|---|---|---|---|---|
| 14 AWG | 4.11 | 2.08 | 15 A | 20 A | 25 A | — | 3.14 | — |
| 12 AWG | 6.53 | 3.31 | 20 A | 25 A | 30 A | 20 A | 1.98 | 3.18 |
| 10 AWG | 10.38 | 5.261 | 30 A | 35 A | 40 A | 30 A | 1.24 | 2 |
| 8 AWG | 16.51 | 8.367 | 40 A | 50 A | 55 A | 40 A | 0.778 | 1.26 |
| 6 AWG | 26.24 | 13.3 | 55 A | 65 A | 75 A | 50 A | 0.491 | 0.808 |
| 4 AWG | 41.74 | 21.15 | 70 A | 85 A | 95 A | 65 A | 0.308 | 0.508 |
| 3 AWG | 52.62 | 26.67 | 85 A | 100 A | 115 A | 75 A | 0.245 | 0.403 |
| 2 AWG | 66.36 | 33.62 | 95 A | 115 A | 130 A | 90 A | 0.194 | 0.319 |
| 1 AWG | 83.69 | 42.41 | 110 A | 130 A | 145 A | 100 A | 0.154 | 0.253 |
| 1/0 AWG | 105.6 | 53.49 | 125 A | 150 A | 170 A | 120 A | 0.122 | 0.201 |
| 2/0 AWG | 133.1 | 67.43 | 145 A | 175 A | 195 A | 135 A | 0.0967 | 0.159 |
| 3/0 AWG | 167.8 | 85.01 | 165 A | 200 A | 225 A | 155 A | 0.0766 | 0.126 |
| 4/0 AWG | 211.6 | 107.2 | 195 A | 230 A | 260 A | 180 A | 0.0608 | 0.1 |
| 250 kcmil | 250 | 127 | 215 A | 255 A | 290 A | 205 A | 0.0515 | 0.0847 |
| 300 kcmil | 300 | 152 | 240 A | 285 A | 320 A | 230 A | 0.0429 | 0.0707 |
| 350 kcmil | 350 | 177 | 260 A | 310 A | 350 A | 250 A | 0.0367 | 0.0605 |
| 400 kcmil | 400 | 203 | 280 A | 335 A | 380 A | 270 A | 0.0321 | 0.0529 |
| 500 kcmil | 500 | 253 | 320 A | 380 A | 430 A | 310 A | 0.0258 | 0.0424 |
| 600 kcmil | 600 | 304 | 350 A | 420 A | 475 A | 340 A | 0.0214 | 0.0353 |
| 700 kcmil | 700 | 355 | 385 A | 460 A | 520 A | 375 A | 0.0184 | 0.0303 |
| 750 kcmil | 750 | 380 | 400 A | 475 A | 535 A | 385 A | 0.0171 | 0.0282 |
Where the derating actually bites
Three situations account for most real derating on residential and light commercial work.
Two circuits in one conduit. That is four current-carrying conductors, so everything in the pipe drops to 80%. It is the cheapest way to lose a circuit rating and the easiest to avoid at rough-in.
A run through insulation or an attic. Attic temperatures above a roof deck are routinely 120 ยฐF in summer, and at 122 ยฐF a 75 ยฐC conductor is down to 75% of its table value.
A panel feed sharing a raceway with everything else. Feeders and sub-feeds in a common conduit stack up fast, and at ten conductors the factor is 50% โ half the table.
None of these are unusual, and none of them show up on a wall chart.
Frequently asked questions
How many amps can 12 gauge wire carry?
20 A at a 60 ยฐC terminal, 25 A at 75 ยฐC and 30 A at 90 ยฐC โ and the circuit is a 20 A circuit in all three cases, because 240.4(D) holds 12 AWG copper to a 20 amp device. The extra table capacity is not spare current you can use; it is headroom that derating eats into before it reaches the ceiling.
When do I have to derate for conduit fill?
Above three current-carrying conductors in the same raceway or cable, and then the factor is 80% for four to six, 70% for seven to nine, and 50% for ten to twenty. Two circuits sharing a pipe is four conductors, so it starts sooner than people expect. Grounds never count, and the neutral of a balanced multiwire branch circuit does not count either.
Does conduit in the sun change the ampacity?
Yes, and by more than most people allow for. A raceway in direct sunlight on a rooftop runs well above air temperature, and once the ambient goes over 86 ยฐF the correction factors start biting: at 104 ยฐF a 75 ยฐC conductor keeps 88% of its rating, at 122 ยฐF only 75%. Underground and in a cool crawlspace it works the other way and you get a little back.
Do the two corrections multiply or do I use the worse one?
They multiply. A hot attic with six conductors in the pipe is the ambient factor times the bundling factor, not whichever is smaller โ 0.88 ร 0.80 is 0.70, so 25 A becomes 17.6. Applying only the worse of the two is the most common derating mistake.
Why is aluminium two sizes bigger for the same amps?
Because it carries about 61% of copper’s current for the same cross-section. 4/0 aluminium and 2/0 copper are both 180 to 175 A at 75 ยฐC โ one step apart in ampacity, two steps apart in size. On feeders the extra diameter usually still costs less than the copper it replaces.
How we calculate this
Worked example
With Conductor 12 AWG, Metal Copper, Temperature column 75 ยฐC โ THWN, most terminals, Ambient 86, Current-carrying conductors together 3, this page works out 25 amps usable. 12 AWG reads 25 A in the table, then ร 1.00 for heat ร 1.00 for bundling
- Largest device this supports20 A
- The same ambient in Celsius30 ยฐC
Sources:
What ampacity is actually measuring
It is a temperature limit, not a fuse. The table current is the current at which the insulation reaches its rated temperature under standard conditions. Nothing dramatic happens one amp above it; the insulation simply ages faster, and it does not recover.
Standard conditions are three conductors at 86 ยฐF. Every real installation departs from that in at least one direction, which is what the correction factors are for.
The lowest-rated part of the path governs. Conductor, terminal, splice, device: the circuit is rated at whichever of them is listed lowest, and it is almost always a terminal.