๐ŸŒก๏ธHow many amps can a wire carry?

โœ“ Tested & verified Updated: How we calculate this

Wire ampacity calculator

°F

25 amps usable

12 AWG reads 25 A in the table, then × 1.00 for heat × 1.00 for bundling

No derating at these conditions

Metal60 °C75 °C90 °C
Copper20 A25 A30 A
Aluminium15 A20 A25 A
Largest device this supports
20 A
The same ambient in Celsius
30 °C

240.4(D) caps this size at 20 A whatever the table says.

Count only current-carrying conductors โ€” the ground never counts.

A sizing aid from the published NEC tables, not a design โ€” have it signed off by a licensed electrician against the code your inspector enforces. Calculations follow the US NEC; outside the US, follow your local electrical code.

One circuit check a month

Monthly

One thing a month worth measuring, testing or recalculating on a home electrical system โ€” the part of sizing that happens after the install. No product pitches, and nothing that needs a live panel.

Free, no account. One click unsubscribes and deletes your address.

Try also

How many amps can a wire carry?

The AmpSizer ampacity result for 12 AWG copper at a 75 ยฐC terminal is 25 amps โ€” and the circuit is still limited to a 20 amp breaker, because 240.4(D) caps small conductors regardless of what the table allows.

Both corrections come off that 25. Put six current-carrying conductors in one raceway and it becomes 20 A. Raise the ambient to 104 ยฐF as well and it becomes 17.6 A, which is below the breaker the circuit was designed around.

This is why the 90 ยฐC column rarely helps. THHN is a 90 ยฐC conductor, but 110.14(C) makes you use the temperature rating of the terminals it lands on, and almost every breaker is listed at 75 ยฐC. The 90 ยฐC figure is the number you derate from, not the one you use.

Both correction tables are below, so you can see the shape of them rather than one factor at a time. The pattern worth remembering is that ambient corrections are gentle until about 100 ยฐF and then steep, while the bundling adjustment falls off a cliff at four conductors and again at ten.

Ambient temperature correction โ€” NEC Table 310.15(B)(1), based on 86 °F (30 °C).
Ambient60 °C wire75 °C wire90 °C wire
50โ€“77 F (10โ€“25 C)× 1.08× 1.05× 1.04
78โ€“86 F (26โ€“30 C)× 1× 1× 1
87โ€“95 F (31โ€“35 C)× 0.91× 0.94× 0.96
96โ€“104 F (36โ€“40 C)× 0.82× 0.88× 0.91
105โ€“113 F (41โ€“45 C)× 0.71× 0.82× 0.87
114โ€“122 F (46โ€“50 C)× 0.58× 0.75× 0.82
123โ€“131 F (51โ€“55 C)× 0.41× 0.67× 0.76
132โ€“140 F (56โ€“60 C)not permitted× 0.58× 0.71
Adjustment for more than three current-carrying conductors bundled together โ€” NEC Table 310.15(C)(1).
Current-carrying conductorsMultiply ampacity by
1 to 3× 1
4 to 6× 0.8
7 to 9× 0.7
10 to 20× 0.5
21 to 30× 0.45
31 to 40× 0.4
41 and more× 0.35

The full ampacity table

Conductor size, area, resistance and allowable ampacity. Ampacity is NEC Table 310.16 โ€” not more than three current-carrying conductors in a raceway, cable or earth, at 86 °F (30 °C) ambient. Correct it for heat and for bundling before you use it.
Sizekcmilmm²Cu 60 °CCu 75 °CCu 90 °CAl 75 °CCu Ω/kftAl Ω/kft
14 AWG4.112.0815 A20 A25 A3.14
12 AWG6.533.3120 A25 A30 A20 A1.983.18
10 AWG10.385.26130 A35 A40 A30 A1.242
8 AWG16.518.36740 A50 A55 A40 A0.7781.26
6 AWG26.2413.355 A65 A75 A50 A0.4910.808
4 AWG41.7421.1570 A85 A95 A65 A0.3080.508
3 AWG52.6226.6785 A100 A115 A75 A0.2450.403
2 AWG66.3633.6295 A115 A130 A90 A0.1940.319
1 AWG83.6942.41110 A130 A145 A100 A0.1540.253
1/0 AWG105.653.49125 A150 A170 A120 A0.1220.201
2/0 AWG133.167.43145 A175 A195 A135 A0.09670.159
3/0 AWG167.885.01165 A200 A225 A155 A0.07660.126
4/0 AWG211.6107.2195 A230 A260 A180 A0.06080.1
250 kcmil250127215 A255 A290 A205 A0.05150.0847
300 kcmil300152240 A285 A320 A230 A0.04290.0707
350 kcmil350177260 A310 A350 A250 A0.03670.0605
400 kcmil400203280 A335 A380 A270 A0.03210.0529
500 kcmil500253320 A380 A430 A310 A0.02580.0424
600 kcmil600304350 A420 A475 A340 A0.02140.0353
700 kcmil700355385 A460 A520 A375 A0.01840.0303
750 kcmil750380400 A475 A535 A385 A0.01710.0282

Where the derating actually bites

Three situations account for most real derating on residential and light commercial work.

Two circuits in one conduit. That is four current-carrying conductors, so everything in the pipe drops to 80%. It is the cheapest way to lose a circuit rating and the easiest to avoid at rough-in.

A run through insulation or an attic. Attic temperatures above a roof deck are routinely 120 ยฐF in summer, and at 122 ยฐF a 75 ยฐC conductor is down to 75% of its table value.

A panel feed sharing a raceway with everything else. Feeders and sub-feeds in a common conduit stack up fast, and at ten conductors the factor is 50% โ€” half the table.

None of these are unusual, and none of them show up on a wall chart.

Frequently asked questions

How many amps can 12 gauge wire carry?

20 A at a 60 ยฐC terminal, 25 A at 75 ยฐC and 30 A at 90 ยฐC โ€” and the circuit is a 20 A circuit in all three cases, because 240.4(D) holds 12 AWG copper to a 20 amp device. The extra table capacity is not spare current you can use; it is headroom that derating eats into before it reaches the ceiling.

When do I have to derate for conduit fill?

Above three current-carrying conductors in the same raceway or cable, and then the factor is 80% for four to six, 70% for seven to nine, and 50% for ten to twenty. Two circuits sharing a pipe is four conductors, so it starts sooner than people expect. Grounds never count, and the neutral of a balanced multiwire branch circuit does not count either.

Does conduit in the sun change the ampacity?

Yes, and by more than most people allow for. A raceway in direct sunlight on a rooftop runs well above air temperature, and once the ambient goes over 86 ยฐF the correction factors start biting: at 104 ยฐF a 75 ยฐC conductor keeps 88% of its rating, at 122 ยฐF only 75%. Underground and in a cool crawlspace it works the other way and you get a little back.

Do the two corrections multiply or do I use the worse one?

They multiply. A hot attic with six conductors in the pipe is the ambient factor times the bundling factor, not whichever is smaller โ€” 0.88 ร— 0.80 is 0.70, so 25 A becomes 17.6. Applying only the worse of the two is the most common derating mistake.

Why is aluminium two sizes bigger for the same amps?

Because it carries about 61% of copper’s current for the same cross-section. 4/0 aluminium and 2/0 copper are both 180 to 175 A at 75 ยฐC โ€” one step apart in ampacity, two steps apart in size. On feeders the extra diameter usually still costs less than the copper it replaces.

How we calculate this

Table ampacity is NEC Table 310.16 โ€” not more than three current-carrying conductors in a raceway, cable or directly buried, at an ambient of 30 ยฐC (86 ยฐF) โ€” for the metal and temperature column you choose. The ambient correction factor is Table 310.15(B)(1), keyed on the conductor’s temperature rating rather than the terminal’s. The bundling adjustment is Table 310.15(C)(1), counted on current-carrying conductors only, with equipment grounding conductors excluded and the neutral of a balanced multiwire branch circuit excluded per 310.15(E). The two factors multiply. The largest device shown is the standard rating from 240.6(A) that does not exceed the corrected ampacity, held down by the small-conductor ceiling of 240.4(D) for 14, 12 and 10 AWG.

Worked example

With Conductor 12 AWG, Metal Copper, Temperature column 75 ยฐC โ€” THWN, most terminals, Ambient 86, Current-carrying conductors together 3, this page works out 25 amps usable. 12 AWG reads 25 A in the table, then ร— 1.00 for heat ร— 1.00 for bundling

  • Largest device this supports20 A
  • The same ambient in Celsius30 ยฐC

Sources:

What ampacity is actually measuring

It is a temperature limit, not a fuse. The table current is the current at which the insulation reaches its rated temperature under standard conditions. Nothing dramatic happens one amp above it; the insulation simply ages faster, and it does not recover.

Standard conditions are three conductors at 86 ยฐF. Every real installation departs from that in at least one direction, which is what the correction factors are for.

The lowest-rated part of the path governs. Conductor, terminal, splice, device: the circuit is rated at whichever of them is listed lowest, and it is almost always a terminal.